30

RT-PRC005-EN

Performance
Data

(6 Ton)

Standard Efficiency

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Table PD-27 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1 HP Standard Motor & Drive

1HP Standard Motor & High Static Drive Kit

(or 2 HP Oversized Motor & Drive)

1920

925

0.95

960

1.03

994

1.11

1026

1.19

1057

1.27

1087

1.36

1116

1.44

1144

1.52

1173

1.61

1200

1.70

2160

944

1.08

978

1.17

1010

1.26

1043

1.36

1073

1.44

1104

1.54

1133

1.63

1162

1.72

1189

1.81

1216

1.91

2400

964

1.22

998

1.32

1030

1.42

1063

1.53

1092

1.63

1123

1.73

1151

1.83

1179

1.93

1206

2.03

1233

2.13

2640

986

1.39

1019

1.49

1051

1.60

1082

1.71

1112

1.81

1141

1.92

1169

2.03

1198

2.15

1225

2.26

2880

1011

1.58

1043

1.69

1073

1.79

1103

1.90

1133

2.02

1161

2.13

1190

2.26

2 HP Oversized Motor & Drive

Table PD-27 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072A3,A4,AW — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Field Supplied

1-HP Standard Motor & Drive

Low Static Drive (1)
1920

573

0.34

630

0.41

680

0.48

726

0.55

769

0.62

811

0.70

851

0.78

889

0.87

2160

548

0.35

602

0.42

656

0.50

706

0.58

751

0.65

792

0.73

832

0.81

871

0.90

908

0.99

2400

584

0.45

635

0.52

682

0.60

732

0.69

777

0.77

818

0.86

856

0.95

893

1.04

930

1.13

2640

569

0.47

621

0.56

670

0.64

715

0.72

758

0.81

802

0.91

845

1.01

883

1.10

919

1.20

953

1.29

2880

612

0.60

660

0.69

706

0.78

749

0.86

789

0.96

830

1.06

870

1.16

909

1.27

945

1.37

979

1.48

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.

Table PD-28 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072A3,A4,AW — Horizontal Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard Motor & Drive

1920

565

0.31

627

0.39

679

0.45

726

0.52

771

0.60

814

0.69

857

0.77

899

0.85

939

0.93

2160

566

0.35

609

0.41

663

0.48

716

0.57

762

0.64

804

0.72

843

0.80

883

0.90

922

0.99

960

1.08

2400

619

0.47

660

0.54

701

0.60

751

0.69

798

0.78

839

0.87

877

0.95

914

1.04

950

1.14

984

1.24

2640

672

0.61

710

0.68

745

0.76

788

0.83

833

0.93

875

1.04

914

1.13

949

1.22

984

1.31

1016

1.42

2880

726

0.77

762

0.86

795

0.94

828

1.02

869

1.11

911

1.21

950

1.33

986

1.44

1019

1.53

1051

1.63

2-HP Oversized
Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop
due to other options/accessories.
1-HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.
2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range
of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product’s warranty will not be
affected.

1-HP Standard Motor
& Field Supplied
Low Static Drive (1
)

1HP Standard Motor & High Static Drive
Kit(or 2 HP Oversized Motor & Drive)

Table PD-28 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

1-HP Standard

1-HP Standard Motor & High Static Drive Kit

Motor& Drive

(or 2 HP oversized Motor& Drive)

1920

978

1.02

1015

1.11

1051

1.20

1086

1.30

1118

1.39

1150

1.49

1180

1.58

1209

1.68

1236

1.77

1263

1.86

2160

996

1.17

1034

1.27

1069

1.36

1103

1.46

1136

1.56

1169

1.67

1199

1.77

1229

1.88

1258

1.98

2400

1020

1.35

1055

1.45

1089

1.55

1122

1.66

1154

1.76

1186

1.86

1216

1.97

1246

2.08

1276

2.20

2640

1049

1.53

1081

1.65

1113

1.76

1144

1.87

1176

1.98

1207

2.10

1237

2.21

2880

1081

1.74

1112

1.86

1141

1.97

1170

2.10

1199

2.22

2-HP Oversized Motor & Drive

Advertising