10 ton), Performance data, High efficiency – Trane RT-PRC005 User Manual

Page 43

Advertising
background image

43

RT-PRC005-EN

(10 Ton)

High Efficiency

Performance
Data

Table PD-52— Belt Drive Evaporator Fan Performance — 10-Ton — THC120A3,A4,AW — Downflow Airflow

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3-HP Standard Motor & Field Supplied Low Static Drive (1)
3200

734

1.03

770

1.17

804

1.31

839

1.45

871

1.60

901

1.74

3600

714

1.02

749

1.14

782

1.27

815

1.41

847

1.57

879

1.73

909

1.89

939

2.04

4000

734

1.16

768

1.30

803

1.44

834

1.58

863

1.72

894

1.87

923

2.04

952

2.21

979

2.39

4400

764

1.36

795

1.49

825

1.63

857

1.79

888

1.95

916

2.10

943

2.25

970

2.41

997

2.59

1024

2.78

4800

828

1.74

857

1.88

884

2.02

913

2.18

942

2.36

970

2.53

996

2.70

1021

2.86

1045

3.03

1070

3.22

3-HP Standard Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.
NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
No accessories or options are included in pressure drop data.
Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
5-HP Fan Motor Heat (MBH) = 2.950 x Fan BHP+.470.
1. Field Supplied Motor Sheave 1VM50 x 7/8 inch, Fan Sheave AK89,

and Belt AX40 required.

Table PD-52 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3200

931

1.89

959

2.06

986

2.22

1012

2.39

1037

2.56

1061

2.74

1084

2.91

1108

3.09

1131

3.28

1153

3.46

3600

969

2.21

997

2.37

1024

2.54

1050

2.72

1074

2.89

1098

3.08

1122

3.27

1145

3.46

1166

3.65

1188

3.85

4000

1007

2.57

1034

2.74

1062

2.93

1087

3.11

1112

3.29

1136

3.47

1159

3.66

1182

3.86

1204

4.07

1226

4.28

4400

1050

2.97

1075

3.17

1101

3.36

1126

3.55

1150

3.75

1173

3.94

1198

4.15

1219

4.34

1241

4.54

1264

4.77

4800

1095

3.42

1119

3.62

1143

3.83

1166

4.05

1189

4.26

1212

4.47

1235

4.68

1258

4.90

1280

5.12

1300

5.32

5-HP Oversized Motor & Drive

Trane’s factory supplied motors, in commercial equipment, are definite purpose
motors, specifically designed and tested to operate reliably and continuously at
all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.

Table PD-53 — Continued

External Static Pressure (Inches of Water)

1.10

1.20

1.30

1.40

1.50

1.60

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

3 HP Standard Motor & Drive

2000

828

1.22

859

1.35

888

1.48

917

1.61

945

1.75

971

1.88

998

2.03

1023

2.19

1048

2.35

1072

2.50

2400

858

1.43

888

1.56

916

1.70

945

1.85

972

1.99

998

2.14

1023

2.29

1050

2.45

1073

2.60

1097

2.76

2800

894

1.65

921

1.79

949

1.95

975

2.11

1001

2.27

1027

2.43

1051

2.59

1076

2.75

1100

2.92

1123

3.09

3200

931

1.89

959

2.06

986

2.22

1012

2.39

1037

2.56

1061

2.74

1084

2.91

1108

3.09

1131

3.28

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 3200 CFM.

NOTES:

NOTES:

NOTES:

NOTES:

NOTES:
Data includes pressure drop due to standard filters and wet coils.
Data does not include pressure drop due to reheat coil.
3-HP Fan Motor Heat (MBH) = 2.900 x Fan BHP+.475.
1. BAYLSDR010A Required.
2. BAYLSDR010A Required.

Trane’s factory supplied motors, in commercial
equipment, are definite purpose motors, specifically
designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our
tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will
not be affected.

Table PD-53— Belt Drive Evaporator Fan Performance—10-Ton— THC120A3,A4,AW— Downflow Airflow— Dehumidification (Hot Gas Reheat)

External Static Pressure (Inches of Water)

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2000

568

0.43

613

0.53

653

0.64

691

0.75

727

0.86

763

0.98

797

1.10

2400

606

0.56

650

0.67

691

0.78

728

0.90

763

1.02

796

1.16

826

1.29

2800

564

0.50

607

0.60

649

0.71

689

0.83

728

0.95

766

1.08

801

1.21

833

1.35

864

1.50

3200

576

0.57

618

0.67

659

0.79

697

0.90

734

1.03

770

1.17

804

1.31

839

1.45

871

1.60

901

1.74

3-HP Standard Motor & Low
Static Drive Accessory Kit (1)

3-HP Standard Motor & Low
Static Drive Accessory Kit (2)

Advertising