Setting battery types on the main unit –2, Figure 3-1, Dip switches (factory setting shown) –2 – Xantrex Technology ENERGY HW 1000 User Manual

Page 32: Setting battery types on the main unit, Warning: fire hazard

Advertising
background image

3–2

975-0467-01-01

Setting Battery Types on the Main Unit

You can attach different types of lead-acid batteries to the

Freedom HW

.

Before installing batteries make sure that you configure the unit to
optimize the charging process.

The settings can be changed by adjusting the dip switches found on the
main unit behind the display panel.

To adjust the battery type setting:

By default (factory setting) the battery type is set to Flooded (OFF|ON).

1. Detach the Display Panel to expose the Dip Switches.

2. Use the tip of your fingernail or a small screw driver with a flat tip to

adjust the switches.

WARNING: Fire hazard

Incorrectly setting the battery type can lead to battery damage and a risk of fire.

Battery
Type

Dip Switch Setting
Switch 1|Switch 2

Bulk/Absorption

Float

Fixed

OFF|OFF

13.5

13.5

Flooded

OFF|ON (factory setting)

14.4

13.5

GEL

ON|OFF

14.2

13.8

AGM

ON|ON

14.3

13.4

Figure 3-1 Dip Switches (Factory Setting Shown)

ON

OFF

Switch 1 | Switch 2

Advertising