Troubleshooting Reference

975-0467-01-01

5–9

No output voltage. The Status
LED is green or yellow.

30 A supplementary
breaker has tripped.

Circuit breaker on the AC
load panel or AC output
disconnect has tripped.

Battery voltage is too low
to start inverting. Display
screen may show DC
voltage as 00.0.

Check load and reset the supplementary
breaker.

Reset the circuit breaker or check the AC
output disconnect circuits.

Check DC connections and cable.
Recharge battery.

No output voltage. The status
LED is not lighting up.

AC shore power is not
available or out of
operating range and the
inverter is in OFF mode.

Check AC shore power.

Turn the inverter ON or change the
inverter setting to Standby mode.

AC shore power is not
available and the inverter
is OFF due to a shutdown
for more than 30 seconds.

Check AC shore power and battery
voltage.

Turn the inverter ON and look at the
display panel for any error code.

See

Table 5-1, “Error Codes Displayed

on the Display Panel Screen” on page
5–5

.

The inverter’s DC input
polarity is reversed.

The inverter was probably damaged due to
the reverse polarity. This type of damage
is NOT covered by the warranty.

Return the unit.

See

Appendix WA, “Return Material

Authorization Policy”

page WA–3

for

information on returning the unit.

The fan turns on and off
during AC shore power
mode.

The battery is
discharged and
demands high current
from the charger.

AC pass-through
current is high.

Do not be alarmed, the unit is performing
normally.

The fan turns on and off
during inverter mode.

The inverter is running
continuously at high
power.

Do not be alarmed, the unit is performing
normally. The fan is activated
automatically.

Table 5-2 Troubleshooting Reference

Problem

Possible Cause

Solution