Xantrex Technology ENERGY HW 1000 User Manual

Page 58

Advertising
background image

5–6

975-0467-01-01

E07

Over-temperature
warning

Inverting

Reduce the loads connected to the AC
outlet of the unit.

Check that the ventilation grille is not
blocked.

Check for ambient temperature and move
the unit to a cooler location whenever
possible.

E08

not used

E09

not used

E10

High battery voltage
(> 15.5 V)

AC shore
power

Check for external charging sources, such
as an over voltage alternator, and
disconnect if necessary.

Confirm that the external charging source is
not the cause. The error may be caused by
the internal battery charger system. Call
Xantrex for support.

E11

Over-temperature
detected on the AC
transfer relay

AC shore
power

Reduce the loads connected to the AC
outlet of the unit.

Check that the ventilation grille is not
blocked.

Check for ambient temperature and move
the unit to a cooler location whenever
possible.

E12

Battery is bad or
external DC load is
connected to the
battery.

AC shore
power

Check the battery bank.
NOTE: The battery voltage did not rise
above 5 Vdc after 1 minute or 10 Vdc after
15 minutes.

Check that the external DC load current
consumption is below the charging current
setting.

Disconnect the DC load or increase the
charger current setting.

Table 5-1 Error Codes Displayed on the Display Panel Screen

Error Code Condition

Mode

Action