Inverter applications –10, Resistive loads –10, Inverter applications – Xantrex Technology ENERGY HW 1000 User Manual

Page 62: Resistive loads

Advertising
background image

5–10

975-0467-01-01

Inverter Applications

The

Freedom HW

performs differently depending on the AC loads

connected to it. If you are having problems with any of your loads, read
this section.

Resistive Loads

These are the loads that the inverter finds the simplest and most efficient
to drive. Voltage and current are in phase (i.e. in step with one another).
Resistive loads usually generate heat in order to accomplish their tasks.
Toasters, coffee pots, and incandescent lights are typical resistive loads. It
is usually impractical to run larger resistive loads—such as electric stoves
and water heaters—from an inverter due to their high current
requirements. Even though the inverter can most likely accommodate the
load, the size of battery bank required would be impractical if the load is
to be run for long periods.

Battery charging current is
lower than the charging set
point during bulk charge
mode.

Ambient (environment)
temperature is high.

Do not be alarmed, the unit is performing
normally. The charging current
automatically de-rates or shuts down at
high ambient temperature. The charger
resumes to normal when the unit’s
temperature cools down.

Improve ventilation. Make sure the unit’s
ventilation openings are not blocked.

Alarm does not sound when
an error is encountered.

Alarm is turned OFF.

Reactivate the alarm. See

“To adjust the

alarm setting:” on page 3–6

.

The problem is not described
in this table.

N/A

Visit www.xantrex.com/support.asp and
check the FAQs (Frequently Asked
Questions) for your product.

Table 5-2 Troubleshooting Reference

Problem

Possible Cause

Solution

Advertising