Operating in Shore Power Mode

975-0467-01-01

4–3

Operating in Shore Power Mode

The

Freedom HW

operates in shore power mode when an AC source (a

generator or utility power) is present at the AC input terminals. When the
AC source is within operating range, the

Freedom HW

unit bypasses

inverter function and provides the same AC source power to the AC
output terminals. AC power will automatically pass through the

Freedom

HW

.

The

Freedom HW

also automatically charges the battery bank that is

connected while in shore power mode. See

“Battery Charging” on

page 4–12

.

The green Status LED lights up to indicate that the

Freedom HW

is using

utility (or generator) power and the battery is full. A flashing green Status
LED indicates that the unit is charging the battery.

Inverter Mode Settings

Inverter mode
setting is
Standby

When the

Freedom HW

’s Inverter mode setting is enabled (“In1”) and

the AC source is outside the operating range or is disconnected, the
transfer switch automatically switches to inverter function. This means
that the AC output terminals will provide power from the battery and any
appliance connected to the AC output terminals will operate.

Inverter mode
setting is Off

When the

Freedom HW

’s Inverter mode setting is disabled (“In0”) and

the AC source is outside the operating range or is disconnected, the

Freedom HW

will not switch to invert mode. This means that even if the

Power button is pressed to try and turn inverter function on, there will be
no power coming from the battery to the AC output terminals. Therefore,
any appliance connected to the AC output terminals will not operate.

WARNING: Shock hazard

Switching the Power button to Standby does not interrupt the supply of shore
power to the

Freedom HW

. Shore power supersedes inverter function. See

“Transitioning from Inverter Mode to Shore Power” on page 4–8

.

Note:

To configure see

“To change the inverter mode

setting:” on page 3–5

.