3 technical data, 1 data – VEGA VEGAPULS 51V…54V User Manual

Page 18

Advertising
background image

18

VEGAPULS 51 V … 54 V

Power supply

Supply voltage

from signal conditioning instrument VEGAMET or
processing system VEGALOG 571
(max. 36 V DC)
fuse 0,5 A

(slow-blow)

Current consumption

max 22,5 mA

Power consumption

max. 80 mW

0,45 VA

Meas. range

1)

Standard

0 … 20 m

Measurement in standpipe

- VEGAPULS 54 on DN 50

0 … 16 m

- VEGAPULS 54 on DN 100

0 … 19 m

Output signal (see "Outputs and processings")

Digital meas. signal (VBUS)

Adjustment

- PC with adjustment software VEGA Visual Operating
- adjustment module MINICOM

Accuracy (typical values under reference conditions)

2)

Linearity error

< 0,1 % (relating to max. meas. range)

Average temperature error

0,03 %/10 K

Accuracy of the 4 … 20 mA

0,25 %

output signal

Resolution

1 mm

Characateristics

Meas. frequency

5,8 GHz (USA 6,3 GHz)

Meas. intervals

1 s

Min. span between

full and empty adjustment

> 10 mm (recommended >50 mm)

Beam angle (at –3 dB)

- VEGAPULS 51 … 53

< 24°

- VEGAPULS 54 with DN 80

38°

- VEGAPULS 54 with DN 100

30°

- VEGAPULS 54 with DN 150

20°

Technical data

2)

Reference conditions acc. to IEC 770:

e.g. temperature 18 … 30°C

1)

Min. distance of the antenna to the medium 5 cm

3 Technical data

3.1 Data