Configuration of the input, ) operating range, ) measuring conditions – VEGA VEGAPULS 51V…54V User Manual

Page 65: ) adjustment

Advertising
background image

VEGAPULS 51 V … 54 V

65

Adjustment without medium

Key adjustment

Display indication

Distance indication
flashes slowly

Adjust-
ment

Para-
meter

Sensor

m(d)

4.700

w.out
medium

Adjust-
ment
in

m(d)

0.0 %

at

m (d)

XX.XXX

(min. adjustment)

OK

OK

+

OK

OK

Set-up

-

Adjustment with MINICOM or VEGAMET

Following short explanations to the set-up
steps 1 … 9.

1. Configuration of the input

First of all you have to inform the signal
conditioning instrument (only VEGAMET
515 V) to which input the sensor is
connected.

2.) Operating range

Without special adjustment, the operating
range corresponds to the meas. range. The
meas. range has already been adjusted with
the min./max. adjustment. Generally it is
useful to choose the operating range slightly
bigger (approx. 5 %) than the meas. range.
Example:
Min./max. adjustment: 0,500 … 3,400 m;
adjust operating range to approx.
0,400 … 3,500 m.

3.) Measuring conditions

see menu plan no. 3) on page 74

4.) Adjustment

Under the menu point "

Adjustment" you inform

the sensor in which meas. range it should
operate.
The adjustment can be carried out with and
without medium. Generally you will carry out
the adjustment without medium as you can
adjust without filling cycle.

Max.

Min.

100 %

(0,500 m level distance)
corresponds to 1200 litres

Meas. range
0,5…3,4 m

0 %

(3,400 m level distance)
corresponds to 45 litres

Advertising