Mounting and installation - Measurement in standpipe

DN 50

ø50

Surge pipe with ball valve

When using a ball valve in a surge pipe, it is
possible to carry out maintenance and
service work without opening the vessel (e.g.
with liquid gas or toxic products).

The ball valve diameter must correspond to
the pipe size and provide a flush surface
when in the open position.

Surge pipe lockable with ball valve

Ball valve

Installation error in surge pipe

Missing ventilation hole

Pipe antenna systems must be provided with
a vent at the upper end of a surge pipe. A
missing hole causes wrong measurements.

Wrong polarization direction

When measuring in a surge pipe, especially
when there are holes for mixing, it is
important that the radar sensor is directed to
the rows of holes. The two rows of holes of
the surge pipe displaced by 180° must be in
one pane with the polarization direction of the
radar signals. The polarization direction is in
the pane of the type plate.

The surge pipe open to the bottom must
have a ventilation hole on top

The polarization direction is in one pane with
the type plate. The sensor must be directed
with the type plate to the rows of holes or the
openings

Correct

Wrong

Type plate