3 adjustment without medium – VEGA VEGAMET 514 User Manual
Page 21
Advertising
VEGAMET 514
21
Settings in the "reduced menu"
Adjustment example
You know the data of the sensor, i.e. you
know that at 0 % filling the sensor delivers a
current of 4.2 mA and at 100 % filling a cur-
rent of 15.5 mA. Enter these values in the
menu items.
6.3 Adjustment without medium
For this adjustment procedure you have to
enter two sensor current values (4 … 20 mA)
corresponding to the levels 0 % and 100 %.
Enter in these two menu items the values of
the senor. Use the [+] and [–] keys to set the
values and [OK] to save the values.
0%
at
mA
4,200
100%
at
mA
15,500
TAG-
No. 1
%
xx,x
Param.
TAG-
No. 1
Ad-
just-
ment
with
medium
without
medium
0%
at
mA
4,000
100%
at
mA
20,000
Meas.
value
indication
15.5 mA at 100 %
4.2 mA at 0 %