3 monitoring – VEGA VEGAMET 514 User Manual

Page 33

Advertising
background image

VEGAMET 514

33

7.3 Monitoring

To activate monitoring, the following
prerequirements must be met:

Meas.
value 50 %

High 5 %

Low –5 %

>55 %

Relay
deenergises

<45%

Settings in the "extended menu"

• Choose in the menu item "

Input from

"

(under the menu item "

Monitoring

") input

4.

• Connect a key switch (opener) to input 4.

Confi-
gura-
tion

Config
inputs

Config
meas.
loop

TAG 1
Level

Appli-
cation

Level

Param.
TAG-
No. 1

TAG -
No. 1
%

xx,x

Monitor-
ing

Input
from

In-
put4

• Choose in the menu range "

Parameter

adjustment relay outputs

" in the menu

item "

Mode

" the mode "

Monitoring

" for the

selected relay.

The selected relay becomes energised. By
pushing the key switch (opener opens), the
actual measured value is first of all frozen
and, derived from this, the relay deenergises
if this value is underrun (Low) or exceeded
(High). After a reset and a repeated pushing
of the keyswitch, the actual measured value
is again frozen.

Param.
TAG-
No. 1

TAG -
No. 1
%
xx,x

Adjust-
ment

Signal
condi-
tioning

Out-
puts

Cur-
rent
out-
puts

Volt
outputs

Relay
outputs

Relay
output
1

prop.
to

Per-
cent

Unit

0,0%

Mode

(Moni-
toring)

Low

%

5,0

High

%

5,0

Moni-
toring

Low &
High

If the monitoring function should be can-
celled, first of all the monitoring must be can-
celled in the menu item "

Mode

". Then the

allocation of the correction input (input 4)
must be cancelled under the menu item
"

Monitoring

".