2 tare – VEGA VEGAMET 514 User Manual
Page 32
32
VEGAMET 514
Settings in the "extended menu"
0
40
100%
40
100%
Meas. values in %
Key
tared course
actual course
actual measured values
tared measured values
7.2 Tare
With the function "Tare" a measured value
beginning at 0 % is created from the actual
measured value. The tare function can be
started via a key connected to correction
signal input 4.
The following steps are necessary to activate
the tare:
• Connect a key (closer) to input 4.
• Choose in the menu item "
Input from
"
(under the menu item "
Tare
") input 4.
• Assign the tared values in the menu item
"
Unit
" to the requested output (e.g. current,
volt, DIS, PC/DCS output, MET indication).
If you want to delete the tare function, you
first have to cancel the tare in the menu item
"
Unit
". Then you have to cancel the allocation
of the correction input (input 4) under the
menu item "
Tare
".
Confi-
gura-
tion
Config
inputs
Config
meas.
loop
TAG 1
Level
Appli-
cation
Level
Param.
TAG-
No. 1
TAG -
No. 1
%
xx,x
Tare
Input
from
In-
put4
Param.
TAG-
No. 1
Adjust-
ment
Signal
condi-
tioning
Out-
puts
Cur-
rent
out-
puts
Volt
out-
puts
Volt
output
1
prop.
to
Per-
cent
Unit
Tare
%
TAG -
No. 1
%
xx,x
Volume
Tare
V%