VEGAMET 514

31

Offset correction

- with unpressurized sensor
- parallel shift of the

adjustement characteris-
tics

Real value correction

- with a given percentage

value

- parallel shift of the

adjustement characteris-
tics

Density correction

- only in conjunction with

hydrostatic pressure
transmitters

- slope correction of the

adjustment characteristics

Offset correction

0

100%

0

100%

corrected measured value e.g. 0 %

Measured value too low

incorrect course of measured values

Measured value too high

actual measured value
in %

Real value correction

Density correction

incorrect course of measured values

incorrect course of measured values

higher density,
measured value too high

smaller density,
measured value too low

0

100%

0

40

100%

40

0

20

100%

0 20

100%

Measured value too low

Measured value too high

actual measured value
in %

actual measured value
in %

corrected measured value e.g. 20 %

corrected measured value e.g. 40 %

Pos. E

Pos. D

Settings in the "extended menu"

DK-correction

-

ε

r

-correction

- only in conjunction with

capacitive measuring
probes

- slope correction of the

adjustment characteristics

DK-correction

0

100%

0

40

100%

40

incorrect course of measured
values

Dielectric constant too large,
Measured value too high

Dielectric constant too small,
Measured value too low

actual measured value
in %

corrected measured value e.g. 40 %

Pos. A

Pos. D

Pos. A

Pos. A

Pos. A

Pos. E