6.7 Simulation

To check outputs and connected instruments,
you can adjust any individual percentage
value with the keys [+] and [–] in this menu
item. Initial point is always the actual meas-
ured value. The indicated value flashes when
simulation is activated. 15 minutes after
setting the simulated value, the simulation
automatically terminates and resets to meas.
value indication.

Settings in the "reduced menu"

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

Signal
condi-
tioning

Out-
puts

Simu-
lation
Now!
OK ?

Simu-
lation

Simu-
lation
%

xx,x

Meas.
value
indication

Overfill protection

Dry run protection

The relay of relay output 1 deenergises at
switching point "Low" (safe switching condi-
tion).

The relay of relay output 1 deenergises at
switching point "High" (safe switching condi-
tion).

Relay output

Parameter

High

Low

High

Low

Parameter

Relay output