5 dimensions, Ex technical data – VEGA VEGAMET 514 User Manual

Page 9

Advertising
background image

VEGAMET 514

9

Ex technical data

Power supply

Operating voltage

U

nom

corresponds to non-Ex version

Reference voltage

U

m

= 250 V AC or 125 V DC

Meas. data input (intrinsically safe circuit)

on VEGAMET 513 Ex 2-times available

Flame proofing

[EEx ia] IIC, [EEx ia] IIB, [EEx ib] IIC or
[EEx ib] IIB

Max. values
- voltage

U

O

= 20 V

- current

I

O

= 128 mA

- power

P

O

= 640 mW

Characteristics

linear

Effective inner inductance L

I

negligible

Effective inner capacitance C

I

negligible

EEx ia IIC

EEx ia IIB

EEx ib IIC

EEx ib IIB

Max. permissible outer inductance L

O

(mH)

0.5

1

1.5

2

2

9

Max. permissible outer capacitance C

O

(nF)

97

78

68

486

200

1000

The intrinsically safe circuits are reliably separated from the non-intrinsically safe circuits up
to a peak value of the nominal voltage of 375 V. The max. voltage on the non-intrinsically
safe circuits should not exceed 250 V

eff

in case of failure.

1.5 Dimensions

Product description

162

100

5,5

15

128,4

25,4

5 TE

Multipoint
connector

Circuit board 100 x 160 x 1.5
European size