VEGA VEGAMET 514 User Manual

Page 41

Advertising
background image

VEGAMET 514

41

Relay mode "overfill protection"

The relay deenergises at switching point
"High" (safe condition).

Relay mode "dry run protection"

The relay deenergises at switching point
"Low" (safe condition).

Relay mode "switching window on"

The relay is energised within the switching
window.

Relay mode "switching window off"

The relay is deenergised within the switching
window.

Relay mode "monitoring"

The selected relay energises. By pushing the
key switch (opener), the actual measured
value is first of all frozen and, derived from
this, the relay deenergises of this value is
underrun (Low) or exceeded (High). After a
reset and a repeated pushing of the key
switch, the actual measured value is again
frozen.

Settings in the "extended menu"

d

t

b z

High

Low

Parameter

d

t

b z

High

Low

Parameter

d

t

b z

High

Low

Parameter

d

t

b z

High

Low

Relay output

Parameter

Meas.
value 50 % High 5 %

Low –5 %

>55 %

Relay
deenergised

<45%

Relay output

Relay output

Relay output

Advertising