4 technical data – VEGA VEGAMET 514 User Manual

Page 6

Advertising
background image

6

VEGAMET 514

1.4 Technical data

Power supply

Operating voltage

U

nom

= 24 V AC (20 … 53 V), 50/60 Hz
= 24 V DC (20 … 72 V)

Power consumption

approx. 6 VA or approx. 4 W

Meas. data input

Number

1 input

Input type

active two-wire input, analogue (sensor is

powered by VEGAMET)

Range

4 … 20 mA

Sensor

capacitive electrodes, pressure transmitters,
process pressure transmitters, differential
pressure transmitters

Voltage
- at 4 mA

approx. 18 V DC

- at 20 mA

approx. 15 V DC

Current limitation

at approx. 26 mA, short-circuit-proof

Detection line break

< 3.6 mA

Detection short-circuit

> 21 mA

Min. adjustment delta

2 % of the entered sensor values

Connection cable

2-wire standard cable (screening
recommended)

max. resistance per wire

35

Resolution

1 µA

Linearity error

0.025 % at 4 … 20 mA

Temperature error

0.04 %/10 K at 4 … 20 mA

Correction signal input

Number

1 input

Function

switching signal for triggering corrections

or special relay modes via
external switching contact

Voltage

5 V (from instrument)

Current

5 mA

External cable resistance

≤€

150

Current output

Number

1 output

Function

analogue output of the processing results

Range

adjustable between 0 … 20 mA

Load

max. 500

Resolution

1 µA

Linearity error

0.05 % (relating to 20 mA)

Temperature error

0.05 %/10 K (relating to 20 mA)

Product description