VEGA VEGAMET 514 User Manual

Page 54

Advertising
background image

54

VEGAMET 514

E034

Instrument error. A serious error was detected on the instrument (possibly
defective EEPROM). Disconnect voltage and then reconnect (cold start). If the
error is not eliminated, please contact your VEGA agency.

E035

Instrument error. A serious error was detected on the instrument (check sum
error in EPROM). Disconnect voltage and then reconnect (cold start). If the
error is not eliminated, please contact your VEGA agency.

E050

Remote VEGAMET not found. The VEGAMET from which a measured value is
expected cannot be found.
Reasons:
- the remote VEGAMET is not connected
- no VEGAMET with this instrument address connected
- line break (DISBUS)
- shortcircuit (DISBUS)
- the remote VEGAMET is defective
- disrupted communication (DISBUS)
Probably
- failure in the DISBUS transmitter/receiver part of VEGAMET
Please check the instrument address on both VEGAMETs, the connection
cable, the remote VEGAMET and, if necessary, this VEGAMET.

E051

Failure during transmission of measured values via DISBUS. It is not possible
to receive a valid measured value via DISBUS from the remote VEGAMET; the
communication to the remote VEGAMET, however, is okay.
Reason:
- failure on remote VEGAMET
- the input of the remote VEGAMET, which should be transmitted to, is not yet
configured
Please check the remote VEGAMET and, if necessary, its input configuration.

E052

The input number of the VEGAMET from which a measured value is expected
has not yet been assigned.

E053

Span of the sensor characteristics values too small. The sensor characteristics
values are too close together or are identical.

E054

Sensor characteristics values reversed. The min. sensor characteristics value
is higher than the max. sensor characteristics value.

E060

Span of the current output values too small. The values for the current output
are too close togehter or are identical. Please check the adjustment of the
current output.

Error code

Meaning

Diagnostics

Advertising