3 configuration of measuring systems – VEGA VEGAPULS 81 User Manual

Page 10

Advertising
background image

10

VEGAPULS 64 and 81

Types and versions: Configuration of measuring systems

Measuring system with one VEGAPULS 64 sensor (compact instrument)

• Analogue, standardized 0 … 20 mA-current signal as signal output. For adjustment, a digital

adjustment signal is superimposed to the 0 … 20 mA-sensor signal.

• Adjustment and parameter adjustment via a PC and the adjustment program VVO. For adjust-

ment the PC is connected via the adapter VEGACONNECT to the 0 … 20 mA-signal line.

• Optionally an external digital/analogue indication. The indication can be separated from the

sensor up to 25 m.

• The max. permissible resistance (load) of the 0 … 20 mA-signal output is 500

.

In case the input resistors of the processing systems connected to the 0 … 20 mA-signal output

are less than 100

, a resistor of more than 100

must be switched into the 0 ... 20 mA signal

line for the adjustment period.

The digital adjustment signal is short-circuited or damped via too small input resistors so that the
digital communication with the PC would no more be ensured.

2

2

2

+

0 … 20 mA signal

output and static
digital adjustment

signal

Resistor

100

VEGACONNECT

PC with adjustment
software VEGA Visual

Operating

VEGAPULS 64 FK
with integral

processing

2.3 Configuration of measuring systems

A measuring system of sensors with a 0 … 20 mA signal output (compact instrument) consists

only of one sensor. For sensors with digital signal output, the measuring system consists of one

sensor and one VEGAMET signal conditioning instrument or the VEGALOG Processing system.

On this page and the following ones you will see measuring systems with sensors providing a
level proportional 0 ... 20 mA current (compact instruments) as output signal.

On the following pages you will see measuring systems with sensors delivering a digital signal a

VEGAMET signal conditioning instrument or to the VEGALOG Processing system. Signal condi-

tioning instrument or Processing system deliver with these sensors various level proportional
output signals such as 0 … 20 mA currents, 0 … 10 V voltage or switching signals (relay) .