VEGA VEGAPULS 81 User Manual

Page 69

Advertising
background image

VEGAPULS 64 and 81

69

Adjustment steps with the signal con-
ditioning instrument

You adjust the signal conditioning instrument

and the sensor with the six keys on the signal

conditioning instrument (–; +;

;

; ESC; OK).

The basic set-up steps:

- First create a new measurement loop with

the menu “

Configuration / Configuration

measurement loop“

- Then co-ordinate the sensor to an input of

the signal conditioning instrument in the

menu “

Configuration / Configuration inputs /

Input no.…“

- In the submenu “Sensor optimization“ out of

the menu “Configuration / Configuration
inputs“ you then carry out the configuration

and parameter adjustment of the sensor.

Hence the set-up of the radar sensor is carried

out. In the main menu “Parameter adjustment“
and in the menu “Configuration / Configuration

outputs“ you choose how the sensor values

should be processed and provided. E.g. you

carry out the adjustment, the scaling, the
parameter adjustment, the current outputs or

the adjustment of the relay functions.

First set-up with the signal condition-
ing instrument

After you have connected the radar sensor (s)

with a screened two-wire cable to the signal

conditioning instrument VEGAMET 514 V or

515 V switch on the power supply for the sig-
nal conditioning instrument. The signal condi-

tioning instrument powers then the sensor (s)

with energy.

Types C, D and E of VEGAPULS 81 series are
powered separately. Connect the sensors like

the signal conditioning instrument to the power

supply.

Fault signals

Normally you get fault signals. This is normal

for the first set-up. Hence carry out an instru-

ment reset first before you create a measure-

ment loop and you carry out the parameter

adjustment.

Set-up: Adjustment with signal conditioning instrument

Reset

Carry out a reset first to provide a defined

instrument condition. Proceed acc. to the

following steps: Push the left key until in the

display (right) the appropriate indication ap-

pears. “OK…OK“ means that you have to push
“OK“ until the requested indication appears in

the display.

Key:

Display:

OK…OK The fault signal disappears. First the

measurement loop (TAG) without

measured value is indicated.

OK

Then parameter TAG1…3 appears.

Note:

If no adjustment is made for appr. 15 seconds,

the indication jumps back to the stage of the

measured value indication or to the fault sig-

nal. Then push again “

OK“ until the fault signal

extinguishes.

Additional functions

OK

Password off

Reset VEGAMET

OK

Reset configuration

OK

To default

OK

Reset OK?

OK

Reset now OK?

OK

The indication flashed and VEGAMET is reset

to the default values.

Linked application

OK

delete all MST

OK

Reset OK?

OK

Reset now OK?

OK

The indication flashes and all measurement

loops are reset to linked application. The menu

Linked application“ appears again.

If you want to carry out a differential measure-
ment with two sensors, the following adjust-

ments are necessary. Continue your adjust-

ment under “

Quit reset menu“. However if you

need single measurements, continue with the

adjustment.