VEGAPULS 64 and 81

49

Electrical connection

5 Electrical connection

5.1 Connection and connection

cable

Safety information

Ensure that the instrument is unpressurized

before you start work. Always switch off the

power supply before you carry out clamping
work on the radar sensors. Protect yourself

and the instruments.

Skilled staff

Instruments which are not operated with a
protective low voltage must only be connected

by skilled staff.

Connection

A standard two-wire cable can be used as

connection for the output signal. Very often the
“electromagnetic pollution“ by electronic ac-

tuators, energy transmission and transmitting

stations is so considerable that the two-wire

cable for the output signals (digital or ana-
logue) should be screened.

We recommend to use a screening. This

screening prevents against future interfer-

ences. Earth the screen of the signal line al-
ways at one sensor side and use a low imped-

ance earth connection (foundation, plate or

mains earth).

Ex-protection

If an instrument is used in hazardous areas,

the appropriate regulations, conformity certifi-

cates and type approvals for systems in Ex-
areas must be noted (e.g. DIN 0165).

Intrinsically safe circuits with more than one

active facility (instrument delivering electrical

energy) must not be connected. Note the
special installation regulations (DIN 0165).

Connection cable

Note that the connection cable must be speci-

fied for the expected operating temperatures

in your systems.

Cables with intrinsically safe circuits must be

marked (blue) and must not be used for other

circuits.