VEGA VEGAPULS 81 User Manual

Page 76

Advertising
background image

76

VEGAPULS 64 and 81

Parameter adjustment TAG…

Outputs

Relay outputs (1 or 2)

Type (B)

–– Type :

(push “OK“ and choose with “+“ and “–“ the

requested relay function off)

• Raising tendency

The relay of relay output 1 de-energizes

when the raising average value out of

“t ges.“ exceeds the previously defined

%-value.

• Falling tendency

same function, however with falling

average value.

–– Deviation in %

2

If the level change exceeds this adjusted %-value,

the tendency determination responds. 0 … 110 %,

example 2 % (modification) per t ges.

–– Deviation per time

–– Scanning time in s 60

Adjustment range 0 … 999 s

Example 60 s corresponds to 1 minute

–– Number of

scannings

4

Adjustment range 0 … 99 steps

Example: t ges = ta • n = 60 • 4 = 240 s = 4 min.,

i.e. after every 4 minutes the average value of the

deviation is generated and the result is compared
with the given deviation in %, here in the example

2 %.

Set-up: Menu survey of the signal conditioning instrument

d b z

t

%

1

2

3

4

ta

t ges.

n = 4

Relay outp.

ta = scanning time

n = number of scannings

d b z

t

1

2

3

4

ta

t ges.

n = 4

%

Relay outp.

ta = scanning time

n = number of scannings