GE Industrial Solutions TLE Series 225-500 User Manual User Manual

Page 25

Advertising
background image

Critical Power

Modifications reserved

Page 25/90

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx

User Manual TLE Series 225 - 500 UL S1

LED ALARM (yellow color)

It blinks when one or more alarm is activated. The internal Buzzer is ON.

The LED remains blinking (with the alarm condition still present) and the buzzer stops when the key
“MUTE” is pressed.

The LED ALARM is also lighted when the Load is not protected by UPS or in case Q1 is open.

LED STOP OPERATION (red color)

It warns about the imminent inverter stop (default parameter = 3 min.) and the consequent Load shut-
down as result of:

The battery is fully discharged and the Load cannot be transferred on Utility.

Overtemperature or overload condition (>125%) and the Load cannot be transferred on Utility.

Bypass
Data regarding Bypass.
See Section 6.2.

Rectifier
Data regarding Rectifier.
See Section 6.2.

Load output
Data regarding Load.
See Section 6.2.

Battery
Data regarding Battery.
See Section 6.2.

Green color: indicates battery charged.

Yellow color: indicates STOP OPERATION status.

Red color:

indicates low battery.

LEDs on Synoptic Diagram
LED 1

Rectifier

LED 2

Inverter

LED 3

Booster/Battery charger

LED 4

Automatic Bypass

LED 5

LOAD

Examples of typical scenarios in the Synoptic Diagram:

Load supplied by Inverter

Load supplied by Automatic Bypass

Load supplied by Manual Bypass Q2

Load supplied by Battery