User Manual TLE Series 225 - 500 UL S1

6.3.1 Events (alarms and messages)

Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with
the software “GE Data Protection” installed or with the monitoring system “GE iUPSGuard”.

Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signaled with the LED ALARM and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED ALARM and the acoustical alarm).

6.3.2 Alarms list

Code

Alarm

Description

4000

SETUP VALUES LOST

Parameters are lost and have been replaced with
default values.
Please call nearest Service Center for intervention.

4001

REGULATION BOARD FAILURE

A blocked DSP on the Control board causes this
alarm, and consequently the shut-down of Rectifier
and inverter and the opening of K3.

4004

UPS FAILURE ON PARALLEL SYSTEM

The master unit detected the slave unit missing on
the communication bus even though switch Q1 is
still closed.

4006

BUS JA CRC FAILURE

The parallel communication bus system is subject
to high errors rate on channel JA.

4007

BUS JB CRC FAILURE

The parallel communication bus system is subject
to high errors rate on channel JB.

4008

BUS JA FAILURE

There is an interruption in the channel JA of the
parallel communication bus system.

4009

BUS JB FAILURE

There is an interruption in the channel JB of the
parallel communication bus system.

4010

CONNECTIVITY BUS FAILURE

The connectivity communication bus is faulty or
interrupted.

4100

RECTIFIER FUSES FAILURE

The u-switch mounted on the Rectifier input fuses
indicates a blown fuse, and consequently it is shut
down.
Clearance of this condition allows you to restart
the Rectifier.

4102

K4 CLOSING FAILURE

K4 not closed despite a closing command being
issued.
Signaled by auxiliary contact. Rectifier cannot start.

4103

K4 OPENING FAILURE

K4 not open despite an opening command being
issued.
Signaled by auxiliary contact.
Utility remains connected to Rectifier bridge.

4104

BATTERY FUSES FAILURE

This

function,

when

enabled

on

input

programmable relays (password required), warns
the user about the external Battery Fuses failure or
MCB opening, Signaled by NO free contact.

4105

RECTIFIER OVERTEMPERATURE

Temperature sensor indicates a situation of
overtemperature on the Rectifier bridge.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start as
long as this condition persists.