GE Industrial Solutions TLE Series 225-500 User Manual User Manual

Page 43

Advertising
background image

Critical Power

Modifications reserved

Page 43/90

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx

User Manual TLE Series 225 - 500 UL S1

HOURS/DAY
The number of eBoost™ Operation Mode hours per weekday “Monday to Sunday” is displayed in the
operation mode parameter window (ceiling value).

NOTE !

To avoid undesired eBoost™ Operation Mode, verify:

Date and Time.

eBoost™ screen how many hours of eBoost™ Operation Mode have been
selected for each day of the week.

NOTE !

The eBoost™ Operation Mode will become active only if the Load is supplied from
the Inverter
.
eBoost™ Operation Mode
is only possible if the UPS load exceeds a minimum
threshold (default 10% of the rated capacity).
In case no-load conditions, or anyway below said threshold, the UPS operates in VFI
mode
.



TOUCH SCREEN

This screen permits the adjustment
(“CALIBRATE” key) of the LCD’s “Touch
Screen”
sensitivity.



IDENTIFICATION SCREEN

ID
Number of UPS in the RPA Parallel
System (0 for single unit).

Model
UPS model, power range and series
number.

S/N
The UPS serial number.

UPS SW version
The UPS software version.

Display SW version
The LCD display software version.