User Manual TLE Series 225 - 500 UL S1

Code

Alarm

Description

4146

4TH LEG DRIVER FAILURE

The Booster’s driver indicates the presence of a
defect which switches the power off.

4147

BATTERY CHARGER DRIVER FAILURE

The Battery charger driver indicates a defect,
switching it off.

4150

BOOSTER OVERTEMPERATURE

The temperature of the booster bridge exceeds
the machine’s set limit or the coil’s sensor is on.

4151

4TH LEG OVERTEMPERATURE

The temperature of the 4

th

leg’s bridge exceeds

the machine’s set limit.

4301

INVERTER FUSES

The alarm signals an inverter outlet fuses fault,
causing it to switch off immediately.
It may only be manually switched on after the
alarm has ceased.

4304

K7 CLOSING FAILURE

K7 not closed despite a closing command.
Signaled by auxiliary contact.
Load will be supplied by Utility.

4305

K7 OPENING FAILURE

K7 not open despite an opening command.
Signaled by auxiliary contact.
Load will be supplied by Utility.

4307

INVERTER TRANSFORMER

OVERTEMPERATURE

The temperature sensor of the Inverter
Transformer indicates overtemperature.
Elapsed “stop operation” time, Inverter shut-
down.
With Utility OK, Load is transferred on Utility.

4308

DC FUSES FAILURE

Blown input DC fuse(s) F1 of the Inverter.
Inverter cannot be started as long as present.

4309

DRIVER FAILURE

An abnormal condition has been detected on one
or more power modules of the Inverter
(temperature or overcurrent).
Inverter shut-down and cannot be started as
long as the alarm is present.

4310

IGBT RECTIFIER DRIVER FAILURE

Indicates a failure on the driver board or the
Rectifier IGBT bridge.
The Rectifier is shut-down.

4311

BOOSTER DRIVER FAILURE

Driver Booster error signal.

4312

INVERTER VOLTAGE OUT

OF TOLERANCE

Inverter Output Voltage is out of the tolerances (

10%).
Inverter is switched OFF.

4320

ISMAX DETECTION

Detection of Inverter Bridge (Is) current limit
causing the Inverter OFF and automatic re-start.
After 3 times the Inverter switches-Off, and it can
be restarted manually.

4321

HIGH CURRENT SHARING

A high exchange current value is detected
between the UPS of the Parallel System.