3 messages list, Messages list – GE Industrial Solutions TLE Series 225-500 User Manual User Manual

Page 37

Advertising
background image

Critical Power

Modifications reserved

Page 37/90

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx

User Manual TLE Series 225 - 500 UL S1

6.3.3 Messages list

Code

Message

Description

4002

WATCHDOG RESET

The microprocessor has detected an incorrect
operation:
Transfers the load on utility and performs a
program reset.
The inverter will restart automatically and will
supply the load.

4003

SENSOR AUTO-CALIBRATION ERROR

The voltage/current reading were not correctly
calibrated when the UPS was switched on.

4111

RECTIFIER UTILITY OK

Rectifier Input Utility is again within the admitted
tolerance (voltage, frequency and phase).

4119

BATTERY TEST STARTED

Start of Manual or Automatic Battery Test.

4120

BATTERY TEST STOPPED

End of Manual or Automatic Battery Test.

4122

MANUAL BOOST CHARGE START

Recharging has been manually activated from
the control panel, bringing the final load up to the
value of the respective parameter.

4123

AUTOMATIC BOOST CHARGE START

After the battery has discharged, an automatic
boost charge has started to recharge the battery
based on pre-defined settings.

4124

MANUAL/AUTOMATIC BOOST CHARGE

STOP

The automatic boost charge has finished. The
battery’s voltage will return to the maintenance
value.
A manually activated boost charge will finish if: it
is manually interrupted, the initial timer setting
has expired, or the rectifier is not functioning
correctly (Alarm 4140).
The battery voltage will return to the
maintenance value.

4144

BOOSTER ON

The booster is switched ON.
It transfers energy from the battery to the DC-
link.

4145

BOOSTER OFF

The booster is switched Off.

4148

BATTERY CHARGER ON

The battery charger is switched on and is
charging the battery.

4149

BATTERY CHARGER OFF

The battery charger is switched off.

4161

RECTIFIER ON

Rectifier started.

4162

RECTIFIER OFF

Rectifier shut-down.

4163

GENERATOR ON

Customer Interface (X1 - 11, 22) received a Gen-
set ON signal.
Operating mode depend on setting of
Parameters.

4164

GENERATOR OFF

Customer Interface (X1 - 11, 22) received a Gen-
set OFF signal.
Function Bypass enabled depends on setting of
Parameter.

4302

INVERTER CANNOT BE TURNED ON

Inverter cannot be switched on because one of
the following conditions is still present:
- Overtemperature

- K7 opening Failure

- Low Battery Voltage - High Battery Voltage
- Inverter Fuses

- DC Low

- Overload

- EPO (Emergency Power Off)