User Manual TLE Series 225 - 500 UL S1

Code

Alarm

Description

4106

RECTIFIER TRANSFORMER

OVERTEMPERATURE

The temperature sensor inside the input
transformer

winding

indicates

overtemperature.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start
as long as this condition persists.

4110

RECTIFIER UTILITY OUT OF TOLERANCE

Rectifier Input Utility is out of tolerance
(voltage, frequency or phase).

4115

LOW BATTERY VOLTAGE

The Battery has been discharged and reached
“stop operation” time-out (default 3 minutes),
and the Inverter will be shut down.
It will restart automatically only when the
Battery has recharged enough for a minimum
runtime.

4116

HIGH BATTERY VOLTAGE

Dangerous high DC Voltage caused inverter
shut-down.
Inverter restarts automatically after Battery
returns to floating voltage.

4117

BATTERY EARTH FAULT

A leakage current to earth has been detected
on the DC circuit.

4118

BATTERY FAULT

During battery test the voltage falls under the
critical level (depending setting parameters).
Battery test is stopped.

4121

HIGH DC RIPPLE

A high ripple is present in the battery voltage.

4125

HIGH DC-LINK VOLTAGE

Detection of high voltage on the DC-link.
The rectifier, booster and inverter will switch off
for protection purposes.
The rectifier may only be switched on again if
the DC-Link’s voltage value falls below 430V.

4126

4

th

LEG CONTROL SATURATION (Imax)

The current in the fourth leg has reached its
highest value.

4130

TURN ON RECT. OR SHUTDOWN UPS

Rectifier and Inverter are OFF.
The DC power supply is discharging the
Battery.
Rectifier must be restarted or Battery must be
disconnected in order to avoid damage.

4140

RECTIFIER CONTROL FAILURE

Rectifier Voltage hasn’t reached the set value
(probably fault on regulation loop).
LED Rectifier on control panel is blinking.

4141

ISMAX DETECTION RECTIFIER

After 3 IS-Max condition within the time frame
specified in respective parameter, the Rectifier
remains shut-down.

4142

RECTIFIER CURRENT MAX

Will cause immediate shut-down of the
Rectifier.
Based on the value inserted in the respective
parameter.

4143

BOOSTER/BATTERY CHARGER CURRENT

MAX

Detection of maximum current in the
booster/battery charger.
The Booster/Battery charger and Inverter will
switch off for protection purposes.