User Manual TLE Series 225 - 500 UL S1

Code

Message

Description

4303

INVERTER CANNOT BE TURNED OFF

Inverter cannot be switched OFF, because the
Load cannot be switched to Utility (voltage out of
tolerance, not synchronized, BP blocked).

4361

INVERTER ON

The command to start the Inverter has been
activated on the control panel.

4362

INVERTER OFF

The command to switch OFF the Inverter has
been activated by the control panel or
automatically for alarm presence.

4411

BYPASS UTILITY OK

Bypass Input Utility is again within tolerance
(voltage, frequency and phase).

4500

COMMAND LOAD OFF

Disconnection of the Load by opening K6 and K7
for:
EPO / Load Off / Overload / Stop Operation.

4521

NO BYPASS POWER

With the Load supplied by Automatic Bypass, a
Utility Failure or K6 opening occurred.

4534

MULTIPLE LOAD TRANSFER

2 transfers Inverter- Utility have been detected in
a short time (default 30 sec.).

4535

BYPASS LOCKED

Bypass is not available.
Contactor K6 is open, SSM deactivated.

4536

BYPASS FREE

Bypass is enabled.
Contactor K6 is closed.

4561

LOAD OFF

Push-button “Load Off” on the UPS Control Panel
has been pressed, with the output circuit switch
Q1 closed.

4562

DETOUR ON

The auxiliary contact indicates that Manual
Bypass Q2 was closed.

4564

DETOUR OFF

The auxiliary contact indicates that Manual
Bypass Q2 was opened.

4567

COMMAND LOAD ON UTILITY

The control unit received a command to transfer
the Load on Utility.

4568

COMMAND LOAD ON INVERTER

The control unit received a command to transfer
the Load on Inverter.

4572

NO MORE OVERLOAD

End of the overload condition detected with
alarm 4570.

4580

INVERTER AND UTILITY SYNCHRONIZED

The voltages of Inverter and Utility Bypass are
synchronized.

4582

COMMAND NOT TO SYNCHRONIZE

Command not to synchronize with Utility.

4583

COMMAND TO SYNCHRONIZE

Command to synchronize with Utility.

4600

COMMAND UPS ON

The eBoost operation mode function has been
disabled or the programmed time is expired.
The UPS returns to VFI mode supplying the Load
normally by inverter.

4601

COMMAND UPS STAND BY

The function eBoost operation mode is enabled,
and according to the time program the UPS will
run in eBoost mode, supplying the Load normally
by utility.

4602

Q1 OPEN

The auxiliary contact indicates that the output
switch Q1 was opened.

4603

Q1 CLOSED

The auxiliary contact indicates that the output
switch Q1 was closed.