User Manual TLE Series 225 - 500 UL S1

Code

Message

Description

4605

COMMAND IEMi OFF

The IEMi Operation Mode has been disabled or the
programmed time is expired.

4606

eBoost/IEMi ACTIVATION ALLOWED

eBoost/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation
of the functions.

4607

eBoost/IEMi ACTIVATION INHIBITED

Customer Interface Board (X1 - 11, 22) received an
eBoost/IEMi control signal.
eBoost™ Operation Mode and IEMi Operation
Mode will be temporarily inhibited.

4609

eBoost INHIBITED - LOW LOAD

eBoost™ Operation Mode inhibited due to minimal
load not reached.

4699

BATTERY TEST IMPOSSIBLE

Automatic Battery Test is not possible due to:

-

No Utility Rectifier or Bypass.

-

Battery not fully charged.

-

Load is below 10% or above 80%.

Test is postponed for 1 week.

4763

REMOTE CONTROL ON

Inverter can be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both

4764

REMOTE CONTROL OFF

Inverter cannot be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both

4798

SERVICE KEY ACTIVATED

A valid Service Key has been entered.
It will no longer be requested in the next 6 hours.

4799

SERVICE KEY DEACTIVATED

The Service Key validity period has expired.