BATTERY

Capacity (Ah)

Ah capacity of the Battery.

Recharge Mode

Recharge type of the Battery

-

Normal

Valve Regulated Lead Acid Battery (VRLA), NiCd
without boost-charge and Flooded Lead Acid
Battery without boost-charge.

-

NiCd

Nickel Cadmium Battery with boost-charge.

-

Wet Lead Acid Boost

Flooded Lead Acid Battery with boost-charge.

Float Voltage (V)

Voltage to maintain Battery Charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for
confirmation):
Valve Regulated Lead Acid Battery (VRLA):
2.27Vdc for cell

240 cells x 2.27Vdc = 545Vdc
NiCd Battery without boost-charge:
1.41Vdc for cell

284÷309 cells x 1.41Vdc = 401 ÷ 436Vdc
NiCd Battery with boost-charge:
1.41 (1.55 boost-charge) Vdc for cell

281 cells x 1.41Vdc = 397 (436) Vdc
Flooded Lead Acid Battery without boost-charge:
2.23Vdc for cell

180÷195 cells x 2.23Vdc = 402 ÷ 435Vdc
Flooded Lead Acid Battery with boost-charge:
2.23 (2.35 boost-charge) Vdc for cell

180÷185 cells x 2.23Vdc = 402 (423) ÷ 413 (435) Vdc

Recharge Current (A)

Maximum Battery Recharge Current.

Max 20% of battery capacity (Ah).
Example: 100Ah – max. recharging current 20A.

Cells

Number of cells of the Battery, see “Float voltage”.
Example: 240 battery cells

-

40 blocks / 12Vdc Battery

-

80 blocks / 6Vdc Battery

-

240 blocks / 2Vdc Battery

Stop Operation Time
(min)

Residual Battery Autonomy time before UPS forced shut-down.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes.


NOTE !

The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the Battery
Manufacturer
.