User Manual TLE Series 225 - 500 UL S1

7.2 PROCEDURES SINGLE TLE SERIES 225 - 500 FUNCTIONING AS FREQUENCY

CONVERTER

When the TLE Series 225 - 500 functions as a Frequency Converter, the Automatic Bypass and Manual
Bypass
functions are disabled.
Therefore the Load cannot be transferred to Utility in case of overload, short circuit, or Inverter failure.
In situations where the UPS needs to be shut-down for maintenance purposes, also the Load must be
shut-down or disconnected.

7.2.1 Initial Start-up of the TLE Series 225 - 500 as frequency converter

WARNING !

Before proceeding to turn on the UPS system, ensure that the AC and DC external
isolators
are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution
can be powered and all the Output
Isolators
are open.

Open the front door and make sure that:

All the connections to the input/output terminals or bus bars of the UPS have been made correctly.

The safety screens are fixed in their position.

The switches Q1 and CB3 (option) are open (Pos. O) and the external Battery protections must be open
(Pos. O).

TLE Series 225 & 250

TLE Series 400 & 500

LEDs on Synoptic Diagram

Q1

Load output switch

Q2

Manual Bypass switch

CB3

External battery switch (option)

LED 1

Rectifier

LED 2

Inverter

LED 3

Booster/ Battery charger

LED 4 Automatic Bypass
LED 5 LOAD on UPS

LED ALARM

LED LOAD PROTECTED

Command Inverter ON

Command Inverter OFF

Command

System shutdown

Command

System shutdown Reset

1. Switch-ON the Utility voltage from the input distribution.

The UPS performs a “Self-test”.
A successful termination of the tests will be indicated with Overall test
results “OK”.
Commissioning cannot be continued should one or more tests result
to be negative. Please contact in this case your Service Center.

At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.

Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.

Continue

CB3

(Option)

ON

OFF

Q1

I ON

0 OF

F

TLES_UL_225-

250_S1_Switch

Q1-Q2-CB3_02

Q2

I ON

0 OF

F

TLES_UL_400-500_

S1_Switch Q1-Q2_

CB3_02

Q1

I ON

0 OF

F

Q2

I ON

0 OF

F

CB3

(Option)

ON

OFF