Galaxy Vector Controller GCM2, GCM3

Issue 4 January 2008

Product Description 2 - 1

2

Product Description

Overview

The Galaxy Vector Controller is mounted on the inside front
door of a GPS plant with the user interface panel accessible from
the front of the door. See Figure 2-1. In the Flexent Outdoor
system, the controller is installed behind a swing-out control/
display panel. See Figure 2-2. Basic controller specifications are
summarized in Table 2-A.

Table 2-A: Galaxy Vector Controller Specifications

GCM2

GCM3

Input voltage range

19 - 30V

36 - 60V

Maximum input power

4.5W

Form C Alarm contact ratings

60V at 0.3A

Plant voltage measurement accuracy

(±.05% of full scale + 1 count)

±30mV

±40mV

Plant voltage measurement resolution

.01V

Plant current measurement accuracy

±1% of full scale

Plant current measurement resolution

1A

Thermistor temperature measurement accuracy

• ±3°C for battery temperatures

from -5°C to +55°C

• ±5°C for battery temperatures

from -10°C to -5°C

• ±5°C for battery temperatures

from +55°C to +85°C+

Operating temperature range

-40°C to +85°C

Batteryless Operation

The Vector Controller is suitable for use in power plants with or
without batteries. In batteryless plants, the loss of ac power
causes an immediate loss of dc power to the controller and the
activation of all office alarm relays. When ac power is restored,
plant rectifiers will return to their last specified voltage set point,
and the controller will automatically return to its last
configuration.