Blj3 terminal connection board, Figure 2-6: galaxy vector controller blj3 terminal, Connection board – GE Industrial Solutions Galaxy Vector Controller GCM3 User Manual

Page 21

Advertising
background image

Galaxy Vector Controller GCM2, GCM3

Issue 4 January 2008

Product Description 2 - 7

BLJ3 Terminal
Connection Board

Figure 2-6 shows the BLJ3 Terminal Connection Board. Not all
BLJ3 terminals are used by the Vector Controller. The following
pages describe the required connections.

Figure 2-6: Galaxy Vector Controller BLJ3 Terminal Connection Board

Alarm Outputs

Fuses

Contactors

Alarm Inputs

Thermal Inputs

Plant Voltage

Regulation Input

Bay

Alarm Out

Unused

Unused

Unused

Unused

To Modem/

Gateway/

Local Terminal

Front Panel

Control/Display

To Rectifiers

Power In/Out

Shunts 1 and 2

Unused

Vector Controller

Board Not Shown

26 Conductor
Ribbon Cable

Vector Controller Board

(GCM2, GCM3)

System Configuration

DIP Switches

0

1

1

S1

2

3 4

5

6 7

8

S1.2: Software Mode

1,2

S1.3: Option Card Availability

S1.5: Alarm Contact Select

1

S1.7: Power Battery Test

S1.1: Front Panel Configuration

0
1

0
1

0
1

0
1

0
1

- Enabled (shown)
- Disabled

- Standard (shown)
- Flexent Default Configuration Parameters

3

- Modem
- Galaxy Gateway Card (Internet)

S1.4: Rectifier Class

0
1

- Standard GPS Rectifiers
- NP Rectifiers

- Standard HV, High Voltage
- VLV, Very Low Voltage

- Disabled (shown)
- Active

S1.6: - Set to 0

S1.8: - Set to 0

1. Setting both SW1.2 and SW1.5 to "1" will result in activating the HV alarm cont act.
2. SW1.2 setting will only be read by the software when the GCM is powered up.
3. HV alarm contacts used for 2ACF alarm instead of HV alarm.

Advertising