GE Industrial Solutions Galaxy Vector Controller GCM3 User Manual
Page 37
Table 3-A: Alarm Identification Standard Assignments
Description
Alarm
Status
BMW
LED
GVM
Relay
No active alarms present
Norm
Green
None
Very low voltage
Major
Red
None
Battery on discharge
Major
Red
BD
High float voltage
Minor
Yellow
None
Very high voltage
Major
Red
HV
Voltage sense fuse alarm
Major
Red
None
AC fail
Minor
Yellow
ACF
Multiple AC fail
Major
Red
ACF
Rectifier fail
Minor
Yellow
None
Multiple rectifier fail
Major
Red
None
Rectifier ID conflict
Major
Red
None
Rectifier manual off alarm
Minor
Yellow
None
Rectifier AC phase alarm
Minor
Yellow
None
Converter fail
Minor
Yellow
None
Multiple converter fail
Major
Red
None
Converter ID conflict
Minor
Yellow
None
Converter distribution alarm
Major
Red
MJF
Converter fan fail minor
Minor
Yellow
None
Converter fan fail major
Major
Red
None
Fuse alarm major
Major
Red
MJF
Auxiliary input major
Major
Red
None
Load Share imbalance
Minor
Yellow
None
Contactor 1 open
Major
Red
None
Contactor 1 failed
Major
Red
None
Contactor 2 open
Major
Red
None
Contactor 2 failed
Major
Red
None
High battery temperature
Major
Red
None
Temperature probe failure
Minor
Yellow
None
Maintenance open alarm
Major
Red
None
Galaxy Vector Controller GCM2, GCM3
Issue 4 January 2008
Operation 3 - 3