Table 3-A: Alarm Identification Standard Assignments

Description

Alarm

Status

BMW

LED

GVM
Relay

No active alarms present

Norm

Green

None

Very low voltage

Major

Red

None

Battery on discharge

Major

Red

BD

High float voltage

Minor

Yellow

None

Very high voltage

Major

Red

HV

Voltage sense fuse alarm

Major

Red

None

AC fail

Minor

Yellow

ACF

Multiple AC fail

Major

Red

ACF

Rectifier fail

Minor

Yellow

None

Multiple rectifier fail

Major

Red

None

Rectifier ID conflict

Major

Red

None

Rectifier manual off alarm

Minor

Yellow

None

Rectifier AC phase alarm

Minor

Yellow

None

Converter fail

Minor

Yellow

None

Multiple converter fail

Major

Red

None

Converter ID conflict

Minor

Yellow

None

Converter distribution alarm

Major

Red

MJF

Converter fan fail minor

Minor

Yellow

None

Converter fan fail major

Major

Red

None

Fuse alarm major

Major

Red

MJF

Auxiliary input major

Major

Red

None

Load Share imbalance

Minor

Yellow

None

Contactor 1 open

Major

Red

None

Contactor 1 failed

Major

Red

None

Contactor 2 open

Major

Red

None

Contactor 2 failed

Major

Red

None

High battery temperature

Major

Red

None

Temperature probe failure

Minor

Yellow

None

Maintenance open alarm

Major

Red

None

Galaxy Vector Controller GCM2, GCM3

Issue 4 January 2008

Operation 3 - 3

Advertising