Configuring static network parameters, A - 11 – GE Industrial Solutions Galaxy Vector Controller GCM3 User Manual
Page 89
Galaxy Vector Controller GCM2, GCM3
Issue 4 January 2008
Communications Appendix A - 11
Baud
: 9600
Data
: 8
Parity
: none
Stop
: 1
Handshaking: none
Flow Control: none
2. Connect the PC to the Galaxy Gateway card’s local port
(RS-232) connector J2 (if it isn’t already connected).
3. Press reset (SW1 – uP reset; see Figure A-3) on the Galaxy
Gateway card.
4. Wait for any diagnostic messages to pass.
5. Wait for the “ENTER PASSWORD:” command line
prompt.
6. Type the Network Administrator password (default:
networkadm).
7. Wait for the “$” prompt.
Configuring
Static Network
Parameters
After a valid password entry, a login header with the following
format will be displayed:
Board Code
EBW1 1:3 or BJD1 1:2
Serial Number
02DJ09112345
Boot Block
version 1.0
Application Code
version 3.0
Default Web Pages
version 3.0
Custom Web Pages
not found
Ethernet Address
00-60-1D-00-5C-07
IP Address
not configured
Subnet Mask
not configured
Default Gateway
not configured
Host Name
not configured
For assistance type help
$
Typing HELP at the “$” will show all available network
administration commands and command line formats.