Table 3-B: Office Alarm Relay and Front Panel LED Standard Assignments

Asserted Condition

Alarm Relays

Front Panel LEDs

Very high voltage [HV]

PMJE, (HV or none)

MAJ (red)

High float voltage [HFV]

PMNE

MIN (yellow)

Battery on discharge [BD]

PMJE, BD

MAJ (red)

Very low voltage [VLV]

PMJE, (VLV or none)

MAJ (red)

Single ac fail [ACF]

PMNE, ACF

MIN (yellow)

Multiple ac fail [MACF]

PMJE, (2ACF or none)

MAJ (red)

Single rectifier fail [RFA]

PMNE

MIN (yellow)

Multiple rectifier fail [MRFA]

PMJE

MAJ (red)

Single converter fail [CFA]

PMNE

MIN (yellow)

Multiple converter fail [MCFA]

PMJE

MAJ (red)

Major fuse (Controller, FAJ input) [MJF]

PMJE, MJF

MAJ (red)

Low voltage battery disconnect [LVBD]

PMJE

MAJ (red)

Low voltage load disconnect [LVLD]

PMJE

MAJ (red)

LVD1 fail [LVDA]

PMJE

MAJ (red)

LVD2 fail [LVDA]

PMJE

MAJ (red)

Controller fail [CTLR]

PMJE

MAJ (red)

Slope thermal compensation active

LCD

Defective battery temperature probe [TPA]

PMNE

MIN (yellow)

Voltage sense fuse alarm

PMJE

MAJ (red)

Rectifier manual off alarm

PMNE

MIN (yellow)

Rectifier phase alarm

PMNE

MIN (yellow)

Rectifier half power alarm

PMNE

MIN (yellow)

Auxiliary major alarm

PMJE

MAJ (red)

Battery thermal alarm

PMJE

MAJ (red)

Controller unpowered

PMJE, PMNE, MJF, BD,

ACF, HV

Connector open

PMJE, PMNE

MAJ (red)

Alarm cut off

LCD

Display volts

LCD

Display amps

LCD

Galaxy Vector Controller GCM2, GCM3

3 - 4 Operation

Issue 4 January 2008

High Float Voltage Minor Alarm and Very High Voltage
Major Alarm and Shutdown
Because of the importance of protecting the batteries and load
from overvoltage conditions, three high voltage thresholds are
provided. Two are controlled by the Vector and one backup
threshold is hard-wired internally in Lineage Power rectifiers.