Table b-9: converter plant, B - 4, Table b-10: boost management – GE Industrial Solutions Galaxy Vector Controller GCM3 User Manual

Page 96: Table b-11: battery/load contactor

Advertising
background image

Galaxy Vector Controller GCM2, GCM3

Appendix B - 4 T1.317 Objects and Attributes

Issue 4 January 2008

Table B-9: Converter Plant

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

cp1,vdc

Converter output voltage

number

dd.d V

cp1,adc

Converter load current

number

dd.d A

cp1,vsp

Converter float set-point

number

46-57:50V

cp1,dth

Converter disconnect

threshold

number

20-26:21.00V

cp1,rth

Converter reconnect threshold

number

22-26:22.20V

cp1,lvd

Converter low voltage

disconnect

number

0:disable 1:enable

Table B-10: Boost Management

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

bs1,bse

Boost enable

number

0:disable 1:enable

bs1,abe

Auto boost enable

number

0:disable 1:enable

bs1,amf

Auto Boost multiplication

factor

number

1-9

bs1,tmd

Manual boost duration

number

1-250:8 hours

Table B-11: Battery/Load Contactor

Related Commands

OBJ,ATTR

DESCRIPTION

STA

CHA

OPE

TYPE

RANGE OF VALUES

cn1,typ

Contactor 1 type

text

"NONE","LOAD","BATTERY"

cn1,dth

Low voltage disconnect

threshold

number

20-26:21V or 40-52:43.20V

cn1,rth

Low voltage reconnect

threshold

number

20-26:22.20V or 40-52:44.40V

cn2,typ

Contactor 2 type

text

"NONE","LOAD","BATTERY"

cn2,dth

Low voltage disconnect

threshold

number

20-26:21V or 40-52:43.20V

cn2,rth

Low voltage reconnect

threshold

number

20-26:22.20V or 40-52:44.40V

Advertising