BTJ2/BTJ3 Fuses
and Connectors

All fuses are 5A.

F1 – GCM Controller power

F2 – Regulation battery fuse (Vsense)

F3 – LVD power from Charge Bus (Rectifier)

F4 – LVD power from Battery Bus

F5 – Spare

Power connections: Power and sense connections from the
system to the BTJ2/BTJ3 are shown in Table 2-M.

Table 2-M: BTJ2/BTJ3 Power Connections (J21)

Pin

Number

Signal Name

Description

1

Shunt 1 (Chg)

Connection to battery shunt terminal nearest charge
bus (rectifier bus)

2

NC

3

NC

4

Shunt 2 (Chg) Reserved for future use

5

NC

6

NC

7

Controller

Power

Controller power input connection to the charge bus
(rectifier bus)

8

Shunt 1 (Disch)

Connection to the battery shunt terminal nearest the
batteries

9

DG

Controller power input ground

10

Vsense (Grd) Connection to DG bus, remote sense

11

Shunt 2 (Disch) Reserved for future use

12

LVD Battery

Bus

Battery bus power for LVD circuitry on the BTJ2/
BTJ3

13

LVD Charge

Bus

Charge bus power for LVD circuitry on the BTJ2/
BTJ3

14

Vsense (Chg) Connection to the charge bus, remote voltage sense

J2: RJ45 connector for rectifier communication. Pins 1 and 2 are
the communication pair. Pin 3 is isolated ground. Pin 4 is chassis
ground. All rectifiers are connected to this connector in a daisy
chain fashion.