Issue 4 January 2008

Troubleshooting 5 - 1

5

Troubleshooting

Replacing Circuit

Packs

Table 5-A lists the circuit packs available as replacements in the
Vector Controller.

Table 5-A: Replacement Circuit Packs and Temperature Modules

Designation

Description

Ordering

Number

210E

Thermal Probe Multiplexer

107789513

BLJ3

Connection Board

848262622

BMW2

VC Control Panel

108358102

BSM3

Modem Board

108415647

BSM4

Local Port Isolation Board

848501037

BTJ2

+24V Outdoor Connection Board

108629528

BTJ3

-48V Outdoor Connection Board

108963562

EBW1

Gateway Network Card

108340100

GCM2

24V Vector Control Board

108890088

GCM3

48V Vector Control Board

108890096

--

LCD Display Module

848518577

--

Keypad

848569430

BMW2, LCD, Keypad Entire Display Assembly

848597563

Checking the

highest battery

temperature

If temperature probes are connected to the controller and thermal
compensation is enabled, the highest battery temperature can be
calculated based on the plant voltage. Temperatures between the
battery thermal lower temperature and the battery thermal
nominal temperature can be calculated if the raising of system
voltage is also enabled.

Calculate the temperature as follows:


voltage difference


=

(system set point – system voltage reading)

cells per string

where cells per string is the number of 2-volt cells per string.