Galaxy Vector Controller GCM2, GCM3

Issue 4 January 2008

Product Description 2 - 17

J6: Office alarm outputs.

Table 2-P: BTJ2/BTJ3 Office Alarm Relay Output Connections

(J6)

Alarm

Signal

(Note 1)

Description

Pin

Number

PMJ

NO

Power Major Normally open

J6-1

RTN

Power Major Return

J6-2

NC

Power Major Normally closed

J6-3

PMN

NO

Power Minor Normally open

J6-4

RTN

Power Minor Return

J6-5

NC

Power Minor Normally closed

J6-6

BD

NO

Battery on Discharge Normally open

J6-7

RTN

Battery on Discharge Return

J6-8

NC

Battery on Discharge Normally closed

J6-9

MJF

NO

Major Fuse Normally open

J6-10

RTN

Major Fuse Return

J6-11

NC

Major Fuse Normally closed

J6-12

HV/2ACF/VLV

NO

Multiple AC Fail Normally open

J6-14

RTN

Multiple AC Fail Return

J6-15

NC

Multiple AC Fail Normally closed

J6-16

ACF

NO

Single AC Fail Normally open

J6-22

RTN

Single AC Fail Return

J6-23

NC

Single AC Fail Normally closed

J6-24

R O/S

IN

Rectifier On Standby Signal

J6-28

PBT

IN

Plant Battery Test Signal

J6-29

PBT/OS

RTN

Plant Battery Test / Rect On Standby Rtn

J6-30

Note 1: NO (normally open) contacts are open when an alarm state exists.

NC (normally closed) contacts are open when an alarm state exists.

Note 2: Relay assignment is determined by the setting of S1.2 and S1.5:

HV alarm

S1.2-0, S1.5=0

2ACF alarm S1.2=1, S1.5=0

VLV alarm

S1.2=0, S1.5=1

Setting both switches to 1 results in activating HV. The S1.2 setting is only read
during GCM power up.

J27: AMJ (Auxiliary major battery fuse) requires a closure
between pins 1 and 2 to activate alarm.

J28: FAJ (Distribution fuse alarm major) requires bus voltage at
pin 1 to activate alarm. Pin 1 connects to J2 pin 1 of the alarm
board, which provides this alarm signal. The input to the alarm