GE Industrial Solutions Spectra RMS Molded Case User Manual

Page 12

Advertising
background image

GEH-702 Users Manual

11

Catalog Number

Source Voltage Rating

Comments

ADSVMA120Y

120 Vac Wye conn.

to N potential

ADSVMA208Y

208 Vac Wye conn.

to

potential

ADSVMA240D

240 Vac Delta conn.

to

potential

ADSVMA277Y

277 Vac Wye conn.

to N potential

ADSVMA480Y

480 Vac Wye conn.

to

potential

ADSVMA480D

480 Vac Delta conn.

to

potential

ADSVMA600D

600 Vac Delta conn.

to

potential

Catalog Number

No. of Switch Elements

Switch Rating

SAUXGAB1

SAUXGAB2

1 form C

2 form C

Gold-Plated

Contacts

0.5 A @ 30 V


Voltage Modules

For Spectra Series

TM

Switchboard applications involving

Spectra microEntelliGuard

TM

breakers that require

control power and voltage signals, modules are
available that incorporate both the power supply and
voltage conditioner (see Table 9). The modules are 5

“X” units high (6

7

/

8

inches) and mount in 45-inch wide

distribution sections. The modules connect to the
vertical bus bars in the switchboard and provide control
power and voltage signals to the system.

Table 9. Voltage Module Catalog Numbers

Table 10. Distribution Cable Harness Options

Catalog Number

Length (in)

Wire Connectors

SDCHA11

11

12-Pin

SDCHA30

30

12-Pin

SDCHA60

60

12-Pin

Extension cables are used to increase the length of
an existing cable. Because the Spectra
microEntelliGuard

TM

breakers come with both 12-Pin

and 20-Pin wiring harnesses, there are two different
extension cables available.

Table 11. Extension Cable Harness Options

Voltage exchange cables are available and are
necessary for breakers with advanced metering when
installed in group-mounted equipment. These cables
connect between the breaker and the distribution cable
junction box and reverse the voltage signals being

Mounting a distribution cable junction box in the front

input to the breaker (from V

A

V

B

V

C

to V

C

V

B

V

A

). Refer to the

vertical upright of the switchboard across from the

Spectra microEntelliGuard

TM

breaker/trip unit permits

group mounting of the breaker. Group mounted

Spectra breakers with an auxiliary switch that connects
to a junction box require a 1 “X” filler plate adjacent

to the breaker’s right-hand side to accommodate the

auxiliary switch wiring.

Distribution and Extension Cables Interconnection
cables are required if equipment interfaces such as the
distribution cable junction box, power supply plate
assembly, voltage conditioner plate assembly are used.
These cables transmit electronic signals and/or control
power between the various interconnected
components. There are two different types of
interconnection cables available for Spectra
microEntelliGuard

TM

breakers – distribution cables and

extension cables.

Distribution cables are used to interconnect the

junction box, power supply plate assembly, and voltage
conditioner plate assembly. These cables have 12-

Pin connectors and are available in three different
lengths. Table 10 shows the different lengths and their
associated catalog numbers.

Phase Rotation description in the Setup Mode section

of this manual.

Table 12. Voltage Exchange Harness Options

Catalog Number

Length (in)

Wire Connectors

SDCAA6

6

12-Pin

SDCAA6C

6

20-Pin



Auxiliary Switches

An auxiliary switch is used to monitor the state of the
circuit breaker main contacts. Spectra
microEntelliGuard

TM

breakers with communications are

capable of communicating the breaker position when
an auxiliary switch is installed and connected via a
terminal board or junction box. Note: auxiliary switches
with gold plated contacts are required.

Table 13. Auxiliary Switch Options

Catalog Number

Length (in)

Wire Connectors

SDCEA30

30

12-Pin

SDCEA30C

30

20-Pin