GE Industrial Solutions Spectra RMS Molded Case User Manual

Page 27

Advertising
background image

26

GEH-702 Users Manual






Function

Title (as implemented)

Min. Value

Max. Value

Default Setting

Setting Choices





Inputs and Outputs

INPUT 1 (if not RELT optioned)

TRIP

OFF

OFF



RELAY 1



OFF



GROUP 6


OFF [GROUP 6 if

RELT Enabled]

Fixed to GROUP 6 if RELT is optioned, else
available options are GROUP 1 to 5.
GROUP 1: GF Alarm

GROUP 2: Over Current Trip
GROUP 3: Protective Relay Trip
GROUP 4: Load Alarm

GROUP 5: Health Status

GROUP 6: RELT

RELAY 2

OFF

GROUP 6

OFF [GROUP 6 if

RELT Enabled]

Available options are GROUP 1 to 6 if RELT

is optioned, else GROUP 1 to 5

Waveform

Capture


WAVEFORM CAPTURE


DISABLE


ALL


ALL

Available options are:

Disable, Manual, OverCurrent, Protective

Relays, Manual/OverCurrent, Manual/

ProtectiveRelays, OverC urrent/

ProtectiveRelays, All

Frequency

FREQUENCY

50Hz

60Hz

60

50Hz, 60Hz

Operating Voltage

PT VOLTAGE

100

690

480

100 to 690 Volts

steps of 1 Volt

PT CONNECTION

PH-PH

PH-N

PH-PH

PH-PH, PH-N

Power Direction

POWER DIRECTION

UP

DOWN

DOWN

UP, DOWN

Phase Rotation

Setup

PHASE ROTATION

ABC

CBA

ABC

Available Options: ABC, CBA

Thermal Memory

THERMAL MEMORY

YES

NO

NO

YES, NO

Auxiliary Switch

AUX SWITCH INST

YES

NO

NO

YES, NO

Communications

MODBUS BAUDRATE

4800

19200

19200

4800 to 19200 standard baud increments

MODBUS ADDRESS

0

254

1

0 to 254 steps of 1

Date and Time

SET DATE

Y/M/D

SET TIME

H:M:S

Advertising