GE Industrial Solutions Spectra RMS Molded Case User Manual

Page 32

Advertising
background image

GEH-702 Users Manual

31


Table 27. Communication Parameters: Modbus Function 3 (Read/Write Parameters)

Register Address

Variable

Value

Factory Default

Read/Write

206

Neutral Pole Derating

0 - OFF

1 - 50%

2 - 100%

3 - 150%

0

Read/Write


207


ZSI Combination

0

1 - GF

2 - GF&ST

3 - ST

4 - ST & Inst

5 - GF & ST & Inst


0


Read/Write

208

PT Primary Voltage

100 - 690

120

Read/Write

209

PT Connection

0 - Ph-N

1 - Ph-Ph

1

Read/Write

211

Modbus Slave Address

1 - 247

1

Read/Write














213














Communication Setting

0 - 300-8N2

1 - 600-8N2

2 - 1200-8N2

3 - 2400-8N2

4 - 4800-8N2

5 - 9600-8N2

6 - 19200-8N2

7 - 300-8O1

8 - 600-8O1

9 - 1200-8O1

10 - 2400-8O1

11 - 4800-8O1

12 - 9600-8O1

13 - 19200-8O1

14 - 300-8E1

15 - 600-8E1

16 - 1200-8E1

17 - 2400-8E1

18 - 4800-8E1

19 - 9600-8E1

20 - 19200-8E1

21 - 300-8N1

22 - 600-8N1

23 - 1200-8N1

24 - 2400-8N1

25 - 4800-8N1

26 - 9600-8N1

27 - 19200-8N1














27














Read/Write




215




Long Time Trip Pickup

1 - 0.5

2 - 0.55

3 - 0.6

4 - 0.65

5 - 0.7

6 - 0.75

7 - 0.8

8 - 0.85

9 - 0.9

10 - 0.95

11 - 1.0




11




Read/Write