GE Industrial Solutions Spectra RMS Molded Case User Manual
Page 31
30
GEH-702 Users Manual
Table 26. Communication Parameters Modbus Function 3 (Read Only)
Register Address
Variable
Value
Read/Write
2
GF Protection Enable
0 - No
1 - Yes
Read
6
Protective Relay Protections
0 - No
1 - Yes
Read
7
Full Metering Enable
0 - No
1 - Yes
Read
10
Long Time Protection Enable
0 - No
1 - Yes
Read
11
Short Time protection Enable
0 - No
1 - Yes
Read
22
Current Sensor Rating
0 - Invalid
1 - 150A
4 - 400A
5 - 600A
6 - 800A
7 - 1000A
8 - 1200A
Read
23
Neutral Monitoring Enable
(Neutral Pole Protection / 4th Wire)
0 - No
1 - Yes
Read
24
Ground Fault Alarm Enable
0 - No
1 - Yes
Read
35
ZSI
0 - Disable
1 - GF-ST
2- GF-ST-Inst
Read
81
Instantaneous
0 - Disable
1- Switchable
2 - Non-switchable
Read
83
Waveform Capture Enable
0 - No
1 - Yes
Read
107
Reduced Energy Let-Through (RELT)
0 - Disable
1 - Enable
Read