GE Industrial Solutions Spectra RMS Molded Case User Manual

Page 31

Advertising
background image

30

GEH-702 Users Manual


Table 26. Communication Parameters Modbus Function 3 (Read Only)

Register Address

Variable

Value

Read/Write

2

GF Protection Enable

0 - No

1 - Yes

Read

6

Protective Relay Protections

0 - No

1 - Yes

Read

7

Full Metering Enable

0 - No

1 - Yes

Read

10

Long Time Protection Enable

0 - No

1 - Yes

Read

11

Short Time protection Enable

0 - No

1 - Yes

Read

22

Current Sensor Rating

0 - Invalid

1 - 150A

4 - 400A

5 - 600A

6 - 800A

7 - 1000A

8 - 1200A

Read

23

Neutral Monitoring Enable

(Neutral Pole Protection / 4th Wire)

0 - No

1 - Yes

Read

24

Ground Fault Alarm Enable

0 - No

1 - Yes

Read

35

ZSI

0 - Disable

1 - GF-ST

2- GF-ST-Inst

Read

81

Instantaneous

0 - Disable

1- Switchable

2 - Non-switchable

Read

83

Waveform Capture Enable

0 - No

1 - Yes

Read

107

Reduced Energy Let-Through (RELT)

0 - Disable

1 - Enable

Read