GEH-702 Users Manual


Language (Standard)

This setpoint is used to establish the language that is
displayed in the LCD. The available language choices

are English, French, Spanish, German, and Chinese. The
default language is English.


Long Time Pickup (Standard)

This setpoint is used in establishing the breaker’s nominal
ampere rating and is a function of the rating plug installed
in the trip unit. The breaker’s nominal ampere rating “C”,

is calculated by multiplying the long time pickup value

times the rating plug value “X”. The available range of
long time pick up values is 0.5 to 1.0 in increments of 0.05.

Example:

Rating Plug = 800 amps

LT Pickup Setting = 0.50

LT Pickup Value = Nominal Ampere Rating “C” =

800 amps x 0.50 = 400 amps

Figure 8. Long Time Pickup


Long Time Delay (Standard)

This set point is used to allow momentary overloads
without nuisance tripping the breaker. It is also used to
establish the shape of the thermal portion of the time

current curve. Three different long time curve shapes
are available:

MVT > proportional to current squared; same as

Spectra MicroVersaTrip

®

TCC

C > similar to thermal magnetic circuit breaker TCC
F > proportional to current to the fourth power;

similar to fuse TCC

The nominal time delays for each setting are listed below.

Table 15. Nominal Time Delays

Band

Delay (sec)

@ 600%

Band

Delay (sec)

@ 600%

Band

Delay (sec)

@ 300%

MVT1

3

C1

0.3

F1

0.2

MVT2

6

C2

0.5

F2

0.4

MVT3

12

C3

0.8

F3

0.8

MVT4

25

C4

1.2

F4

2

C5

2

F5

4

C6

3

F6

10

C7

5

F7

20

C8

7

C9

12

C10

18

Note: The MVT4, and C10 settings are not available on Spectra G Frame.


Figure 9. Long Time Delay