47


Appendix D. Metering

Table 30. Metering Accuracy

Value

Breaker Full-Scale

Accuracy

1

System Full-Scale

Accuracy

2

Current (A, kA)

± 4%

± 4%

3

Voltage (V)

N/A

± 2%

Real Power (kW, MW)

N/A

± 6%

3

Reactive Power (kVAR)

N/A

± 6%

3

Apparent Power (kVA)

N/A

± 4%

3

Peak Power Demand (kW)

N/A

± 4%

3

Energy (kWh, MWh)

N/A

± 7%

3

Frequency (Hz)

N/A

± 1 Hz

3

Power Factor (%)

N/A

±7% max

1. Includes Trip Unit , breaker current sensors, and rating plug.

2. Includes breaker plus Voltage Module (potential transformers, control power, voltage conditioner).

3. Accuracy performance is based on a loading range of 100% of the breaker current sensors.

For loads below 100% of the breaker currents sensors, add ± 3% to these values.