GEH-702 Users Manual

33



Register Address

Variable

Value

Factory Default

Read/Write







225







Instantaneous Trip Pickup

0 - Off (For switchable Inst only)

1 - Invalid 19 - 10.5

2 - 2.0

20 - 11.0

3 - 2.5

21 - 11.5

4 - 3.0

22 - 12.0

5 - 3.5

23 - 12.5

6 - 4.0

24 - 13.0

7 - 4.5

25 - 13.5

8 - 5.0

26 - 14.0

9 - 5.5

27 - 15.0

10 - 6.0

28 - 16.0

11 - 6.5

29 - 17.0

12 - 7.0

30 - 18.0

13 - 7.5

31 - 19.0

14 - 8.0

32 - 20.5

15 - 8.5

33 - 22.0

16 - 9.0

34 - 23.5

17 - 9.5

35 - 25.0

18 - 10.0

36 - 25.5







2







Read/Write









226









Reduced Instantaneous Trip

Pickup

1 - 1.5

2 - 2

3 - 2.5

4 - 3

5 - 3.5

6 - 4

7 - 4.5

8 - 5

9 - 5.5

10 - 6

11 - 6.5

12 - 7

13 - 7.5

14 - 8

15 - 8.5

16 - 9

17 - 9.5

18 - 10









1









Read/Write

227

Aux Switch Installed

0 - No

1 - Yes

0

Read/Write

228

Phase Direction

0 - ABC

1 - CBA

0

Read/Write



233



GF Trip Pickup

1 - 0.40

2 - 0.41

3 - 0.42

------

59 - 0.98

60 - 0.99

61 - 1.00



61



Read/Write