GE Industrial Solutions Spectra RMS Molded Case User Manual

Page 33

Advertising
background image

32

GEH-702 Users Manual



Register Address

Variable

Value

Factory Default

Read/Write




216




Long Time Trip Delay

0 -

Off

1 -

MVT1

2 -

MVT2

3 -

MVT3

4 -

MVT4

5 -

C- Min

6~14 - C2..C10

15 -

C-Max

16 -

F-Min

17~22 - F2..F7

23 -

F-Max




10




Read/Write

217

Thermal Memory Available

0 - OFF

1 - 12 min. cooling

0

Read/Write

219

Protective Relay Enable

0 - OFF

1 - ON

0

Read/Write

220

Frequency

0 - 50Hz

1 - 60Hz

1

Read/Write








222








Short Time Trip Pickup

1 - 1.5

2 - 2.0

3 - 2.5

4 - 3.0

5 - 3.5

6 - 4.0

7 - 4.5

8 - 5.0

9 - 5.5

10 - 6.0

11 - 6. 5

12 - 7.0

13 - 7.5

14 - 8.0

15 - 8.5

16 - 9.0








1








Read/Write






223






Short Time Trip Delay

0 - Off

1 - Band1

2 - Band2

3 - Band3

4 - Band4

5 - Band5

6 - Band6

7 - Band7

8 - Band8

9 - Band9

10 - Band10

11 - Band11

12 - Band12






5






Read/Write

224

Short Time Kst

0 - 0

1 - 2

2 - 8

3 - 18

0

Read/Write

Advertising